121 LIST OF FUNCTION PARAMETERS功参数表
Function code
功码
Name
名称
Description
说明
Setting range
设置范围
Factory setting
出厂值
Function
Pr000
Speed control mode
速度控制模式
0:Without PG vector control
(PG矢量控制)
1:VF control(VF控制)
0~1
0
Main function parameters
Pr001
Run command channel
操作方式
0:Keypad(LED extinguished)面板
1:Terminal(LED flickering)端子运行
2:Communication(LED light on)通信运行
0~2
0
Pr002
Keypad and terminal
setting
面板端子UPDOWN键设置
0:Effectivethe inverter power down and store调节变频器储存
1:Effectivethe inverter power down but no store调节变频器储存
2:Ineffective调节
0~2
0
Pr003
Frequency order selection
频率命令方式
0:Keypad setting面板设置
1:Analog FV setting模拟FV设置
2:Analog FI setting模拟FI设置
3:Analog FV+FI setting模拟FV+FI设置
4:Multispeed running setting功运行设置
5:PID control setting PID控制设置
6:Remote
control communication setting远程控制
0~6
0
Pr004
Maximum output frequency
输出频率
1000Hz~60000Hz
1000~60000
5000Hz
Pr005
Upper frequency limit
频率
Pr006~ Pr004
Pr006~Pr004
5000Hz
Pr006
Lower frequency limit
频率
000 Hz ~ Pr005
000~Pr005
000Hz
Pr007
Keypad setting frequency
面板设置频率
000 Hz~Pr004
000~Pr004
5000Hz
Pr008
Acceleration time 0
加速时间
01s~36000s
01~36000
Depend on model
厂家设置
Pr009
Deceleration time 0
减速时间
01s~36000s
01~36000
Depend on model
Pr010
Running direction selection
运行方控制
0:Forward 正
1:Reverse 反
2:Forbid reverse 禁止反
0~2
0
Pr011
Carrier frequency setting
载波频率设置
10kHz~150kHz
10~150
Depend on model
Pr012
Motor parameters autotuning
马达参数动调整
0:No action 动作
1:Rotation autotuning 转动动调整
2 Static autotuning 静态动调整
0~2
0
Pr013
Restore parameters
恢复设置
0:No action 动作
1:Restore factory setting恢复出厂设置
2:Clear fault records清错误记录
0~2
0
Pr014
AVR function
AVR功
0:Disabled
1:Enable all the time 总
2:Disabled during deceleration减速时
0~2
2
Pr015
Inverter type
变频器型式
0:G model G模式
1:P model P模式
0~1
0
Drive object parameters
Pr016
Motor rated power
额定功率
04kW~9000kW
04~9000
Depend on model
Pr017
Motor rated frequency
额定频率
001Hz~Pr004
001~Pr004
5000 Hz
Pr018
Motor rated speed
额定转速
0~36000rpm
0~36000
Depend on model
Pr019
Motor rated voltage
额定电压
0V~460V
0~460
Depend on model
Pr020
Motor rated current
额定电流
01A~20000A
01~20000
Depend on model
Pr021
Motor stator resistance
定子电阻
0001Ω~65535Ω
0001~65535
Depend on model
Pr022
Motor rotor resistance
转电阻
0001Ω~65535Ω
0001~65535
Depend on model
Pr023
Motor leakage inductance
漏磁电感
01mH~65535mH
01~65535
Depend on model
Pr024
Motor mutual inductance
互感系数
01mH~65535mH
01~65535
Depend on model
Pr025
Motor without load
空载电流
Pr001~65535A
Pr001~65535
Depend on model
Pr026
Speed pro gain 1
0~100
0~100
20
Vector control parameter
Pr027
Speed loop integration time 1
Pr001~1000s
Pr001~1000
050s
Pr028
Switch lowpoint frequency
转换低点频率
000Hz~Pr031
000~Pr031
500Hz
Pr029
Speed loop progain 2
0~100
0~100
15
Pr030
Speed loop integration time 2
Pr001~1000s
Pr001~1000
100s
Pr031
Switch highpoint frequency
转换高点频率
Pr028~Pr004(Maximum Fre)
Pr028~Pr004
1000Hz
Pr032
VC rotation difference compensation coefficient
50~200
50~200
100
Pr033
Upper Torque limit setting
00~2000(Inverter rated current)
00~2000
1500
Pr034
VF curve setting
0:Straight line VF curue
1:20 nilpotent reduction torque
0~1
0
VF
control parameters
Pr035
Torque boost
00:Automatic)01%~300%
00~300
00%
Pr036
Torque boost deadpoint
00~500(Motor rated frequency)
00~500
200
Pr037
VF rotation difference compensation limit
00~2000
00~2000
1000
Pr038
Auto energy saving selection
0:No action 1:Auto energysaving operation
0~1
0
Pr040
Accelerate time 2
10s~36000s
10~36000
200s
Additional functional parameters
Pr041
Decelerate time 2
10s~36000s
10~36000
200s
Pr042
Inching operation frequency
000Hz~MaxFre(Pr004)
000~Pr004
500Hz
Pr043
Inching operation acceleration
10s~36000s
01~36000
depend on model
Pr044
Inching operation deceleration
10s~36000s
01~36000
depend on model
Pr045
Hopping frequency 1
000Hz~Pr004(MaxFre)
000~Pr004
000Hz
Pr046
Hopping frequency amplitude
000Hz~Pr004(MaxFre)
000~Pr004
000Hz
Pr047
Swing frequency amplitude
00~1000
00~1000
00
Pr048
Instant hopping frequency amplitude
00~500
00~500
00
Pr049
Swing frequency rise time
10s~36000s
01~36000
50s
Pr050
Swing frequency down time
10s~36000s
01~36000
50s
Pr051
Failure autoreset times
0~3
0~3
0
Pr052
Failure autoreset interval time setting
01s~1000s
01~1000
10s
Pr055
Frequency arrival inspection amplitude
00~1000(MaxFre)
00~1000
00
Pr056
Brake value voltage
1150~1400(Standard bus voltage)(380V series)
1150~1400
1300
1150~1400(Standard bus voltage)(220V series)
1150~1400
1200
Pr057
Rotation speed display coefficient
01~9999
01~9999
1000
Pr058
PID preset source selection
0:Keypad giving(Pr059)
1:Analog channel FV giving
2:Analog channel FI giving
3:Remote communication
4:Multiple step giving
0~4
0
PID control parameters
Pr059
Keypad preset PID
00~1000
00~1000
00
Pr060
PID feedback source selection
0:Analog channel FV feedback
1:Analog channel FI feedback
2:FV+FI feedback
3:Remote communication feedback
0~3
0
Pr061
PID output characteristic choice
0:PID output is positive characteristic
1:PID output is negative characteristic
0~1
0
Pr062
Pro gain(Kp)
000~10000
000~10000
100
Pr063
Integration time(Ti)
Pr001~1000s
Pr001~1000
010s
Pr064
Differentiation time(Td)
000s~1000s
000~1000
000s
Pr065
Sampling period(T)
Pr001~10000s
Pr001~10000
010s
Pr066
PID bias limit
00~1000
00~1000
00
Pr067
Feedback breakline detection value
00~1000
00~1000
00
Pr068
Feedback breakline detection time
00s~36000s
00~36000
100s
Pr069
Multistep speed 0
1000~1000
1000~1000
00
Multistep speed control parameters
Pr070
Multistep speed 1
1000~1000
1000~1000
00
Pr071
Multistep speed 2
1000~1000
1000~1000
00
Pr072
Multistep speed 3
1000~1000
1000~1000
00
Pr073
Multistep speed 4
1000~1000
1000~1000
00
Pr074
Multistep speed 5
1000~1000
1000~1000
00
Pr075
Multistep speed 6
1000~1000
1000~1000
00
Pr076
Multistep speed 7
1000~1000
1000~1000
00
Pr077
Motor overload protection
0:Disable
1:Normal motor
2:Variable frequency motor
0~2
2
protection functional parameters
Pr078
Motor overload protection current
200~1200
200~1200
1200
Pr079
Instantaneous powerdown frequencyreduction point
700~1100(Standard bus voltage)
700~1100
800
Pr080
Instantaneous powerdown frequencyreduction ratio
000Hz~ Pr004(Max Fre)
000~Pr004
000Hz
Pr081
Overvoltage stall protection
0:Prohibited protection 1:Allowed protection
0~1
0
Pr082
Overvoltage stall protection voltage
110~140 (Standard bus voltage)
(380V Model)
110~150
120
Pr083
Autocurrent limiting threshod
100~200
100~200
200
Pr084
Frequency decrease rate when current limiting
000Hzs~5000Hzs
000~5000
000Hzs
Pr085
Start mode
0:Start directly
1:DC braking and start
2:Speed tracking and start
0~2
0
Startstop control parameters
Pr086
Starting frequency
000Hz~1000Hz
000~1000
000Hz
Pr087
Hold time of starting frequency
00s~500s
00~500
00s
Pr088
DC Braking current before start
00~1500
00~1500
00
Pr089
DC Braking time before start
00s~500s
00~500
00s
Pr090
Stop mode
0:Deceleration to stop
1:Coast to stop
0~1
0
Pr091
Starting frequency of DC braking
000Hz~1000Hz
000~1000
000Hz
Pr092
Waiting time before DC braking
00s~500s
00~500
00s
Pr093
DC braking current
00~1500
00~1500
00
Pr094
DC braking time
00s~500s
00~500
00s
Pr095
Dead time of FWDREV
00s~36000s
00~36000
00s
Pr096
FWDREV enable option when power on
0: Disabled
1: Enabled
0~1
0
Pr098
S1 terminal function
Programmable multifunctional terminal
0~25
1
Input terminal functional parameters
Pr099
S2 terminal function
Programmable multifunctional terminal
0~25
4
Pr100
S3 terminal function
Programmable multifunctional terminal
0~25
7
Pr101
S4 terminal function
Programmable multifunctional terminal
0~25
0
Pr102
ONOFF filter times
1~10
1~10
5
Pr103
FWDDOWN control mode
0:2wire control mode 1
1:2wire control mode 2
2:3wire control mode 1
3:3wire control mode 2
0~3
0
Pr104
UPDOWN setting change rate
Pr001~5000Hzs
Pr001~5000
050Hzs
Pr105
FV lower limit value
000V~1000V
000~1000
000V
Pr106
FV lower limit corresponding setting
1000~1000
1000~1000
00
Pr107
FV upper limit value
000 V~1000V
000~1000
1000V
Pr108
FV upper limit corresponding setting
1000~1000
1000~1000
1000
Pr109
FV filter time constant
000s~1000s
000~1000
010s
Pr110
FI lower limit value 1
000V~1000V
000~1000
000V
Pr111
FI lower limit corresponding setting
1000~1000
1000~1000
00
Pr112
FI upper limit value
000V~1000V
000~1000
1000V
Pr113
FI upper limit corresponding setting
1000~1000
1000~1000
1000
Pr114
FI filter time constant
000s~1000s
000~1000
010s
Pr115
Y output choice
Opencollector output function
0~10
4
Output terminal functional parameters
Pr116
Relay output choice
Opencollector output function
0~10
3
Pr117
FO output choice
Multifunctional analog quantity output
0~10
0
Pr118
FO output lower choice
00~1000
00~1000
00
Pr119
FO lower limit corresponding output
000V~1000V
000~1000
000V
Pr120
FO output upper limit
00~1000
00~1000
1000
Pr121
FO upper limit corresponding output
000V~1000V
000~1000
1000V
Pr122
User password
0~65535
0~65535
0
Humanmachine interface parameters
Pr125
QUICKJOG
Function select
0:Inching operation
1:Switching of direct and inverse rotation
2:Remove PRGESC setting
0~2
0
Pr126
STOPRST
Function select
0:Valid when keypad control
1:Valid when keypad or terminal control
2:Valid when keypad or communication control
3:Always valid
0~3
0
Pr128
Running status display selection
0~0x7FFF
0~0x7FFF
0xFF
Pr129
Stop status display selection
0~0x1FF
0~0xFF
0xFF
Pr130
Rectify module temperature
0~1000℃
Pr131
Contravariant module temperature
0~1000℃
Pr132
Software version
Pr133
Accumulated running time
0~65535h
0
Pr134
Second latest fault type
0~24
OxFF
Pr135
First latest fault type
0~24
OxFF
Pr136
Latest fault type
0~24
OxFF
Pr137
Output frequency at current fault
Output frequency at current fault
000Hz
Pr138
Output current at current fault
Output current at current fault
00A
Pr139
DC bus voltage at current fault
DC bus voltage at current fault
00V
Pr140
Input terminal status at current fault
This value is a decimal digit numberDisplay the status of all input terminals of the latest failurethe order is:
BIT3
BIT2
BIT1
BIT0
S4 S3 S2 S1
Thenthe input terminals is ON and its relative is 1If the input terminal is OFFits relative is 0You shall know the condition of input signal of the number through this value
0
Pr141
Current failure output terminal status
This value is a decimal digit numberDisplay the status of all input terminals of the latest failurethe order is:
BIT3
BIT2
BIT1
BIT0
R0 Y
Thenthe input terminals is ON and its relative is 1If the input terminal is OFFits relative is 0You shall know the condition of input signal of the number through this value
0
Pr142
Local address
0~2470 is broadcasted address
0~247
1
485 communication parameters
Pr143
Baud rate selection
0:1200BPS
1:2400BPS
2:4800BPS
3:9600BPS
4:19200BPS
5:38400BPS
0~5
3
Pr144
Data bit inspection
and setting
0no parity(N81)for RTU
1even parity(E81)for RTU
2odd parity(O81)for RTU
3 no parity(N82)for RTU
4 even parity(E82)for RTU
5 odd parity(O82)for RTU
6 no parity(N71)for ASCII
7even parity(E71)for ASCII
8odd parity(O71)for ASCII
9 no parity(N72)for ASCII
10evenparity(E72)for ASCII
11odd parity(O72)for ASCII
12no parity(N81)for ASCII
13evenparity(E81)for ASCII
14odd parity(O81)for ASCII
15no parity(N82)for ASCII
16evenparity(E82)for ASCII
17odd parity(O82)for ASCII
0~17
0
Pr145
Communication delay time
0~200ms
0~200
5ms
Pr146
Communication timeout delay
00 s(invalid)01~1000s
0~1000
00 s
Pr147
Treatment action of wrong transmission
0:Alarm and freestop
1:Not alarm and continue operation
2:Not alarm and stop in STOP method(only under communication control method)
3:Not alarm and stop in STOP method(under all control method)
0~3
1
Pr148
Transmission response treatment
0:Writing operation has response
1:Writing operation has no response
0~1
0